综合久久影院-综合久久伊人-综合久久一区二区三区-综合久久五月天-亚洲欧美日韩国产一区图片-亚洲欧美日韩国产一区二区三区精品

Muen
News

News

Enterprise service provider

location : Home > News > Technical information

Use your inverter with the right power

2023-05-20 13:07:17

Low voltage fault


The VFD reports a low voltage fault when the DC link voltage of the drive drops below 62% of the nominal level at the high setting (480 VAC) and 50% of the nominal value of the low setting (400 VAC).


The + 10% and - 15% voltage tolerances in most manuals are recommended operating ranges to allow the driver on hand to maintain high efficiency and proper motor current. The drive can be below these tolerances, but the reduced voltage can have unpredictable effects on motor current, motor temperature and overall performance.


More specifically, if the line voltage parameter of the driver is set to high and 480 VAC is being applied, the driver will generate a low voltage fault when the DC link voltage drops to 62% of the nominal - e.g., 480 VAC · 0.62 · √ 2 = 421 VDC. The nominal DC link voltage is 480 VAC · √ 2 = 679 VDC.


Notes on switching


Although it is generally accepted to switch VFD from line supply to standby generator in many applications, there are some limitations. Most importantly, the phase to phase voltage input voltage swing of many portable standby generators is greater than the phase to phase voltage tolerance recommended by the driver, usually less than 2%. To prevent voltage oscillations, VFDs are equipped with surge protectors in the input rectifier circuits - but external protection (e.g. surge arresters) may be required for severe input disturbances. Large variance will produce large ripple on DC bus capacitance, which will cause capacitor and other power components to be damaged over time.


Another potential problem arises when switching from line power to standby generators. Most drivers take at least two minutes to power up again; failure to follow this guideline may damage the charging relay circuit, or at least damage the input fuse or trip the circuit breaker.


3% line reactor may improve the current surge caused by moderate input power voltage.


Another solution is to add a voltage monitor with an appropriate time delay. They have protection trip levels to shut down the drive in the event of under voltage, over voltage, loss of phase and phase to phase voltage imbalance. These devices ensure that the VFD is not exposed to unbalanced input power or power up until the voltage is within tolerance and the appropriate delay time is met.


Isolation transformer


The final recommendation - the most expensive solution - is to use isolation transformers. This ensures complete isolation of input power issues associated with grounding and noise that may affect the drive. Does isolation transformer provide better protection than line reactor? Yes. When does the application need isolation transformer? This type of transformer is recommended when installed close to the substation.


There are many advantages in inserting driver isolation transformer between VFD and its power supply. Isolation ensures that there is no direct electrical connection between the source and the load - but for any transformer other than an autotransformer. The unique feature of the drive isolation transformer is the grounding electrostatic (Faraday) shield placed between and around the primary and secondary windings. This shielding reduces the capacitance coupling involved in the transmission of common mode voltage interference by one million times. Without this shielding, the capacitor allows high frequency noise and transient voltage spikes to pass through the transformer.


Common mode transients are transients that occur between the ground and the neutral point of an AC system. Although the two parts of a circuit are usually combined at one point, they cannot be considered to have the same potential throughout the power system. The common mode transient interference results from the normal operation of switching power supply, driver operation, arc welding machine, lightning, and even stepping motor. Some isolation transformers also prevent "normal mode" transients between the line and neutral.


Consider an application in which the daily utility power supply of a substation capacitor bank in an industrial park causes a transient voltage spike - amplified by reflection of field capacitors in a nearby factory. Suppose a facility in the park has several small drives rated at 7.5 HP. Normal mode transients can cause these drives to shut themselves down, resulting in costly process downtime. This interruption can be prevented by isolating the transformer.


Frequency converter manufacturer


label

QR code

The public,

Mobile station
The public, Mobile station

Contact

未標題-8.png 0755-81719517
未標題-10.png0755-81719530 未標題-11.pngamb@ambition.com.cn
未標題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

Navigation

Home          About

Product      Case

Solution      Service

Job      News

Contact          

Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號:粵ICP備12045920號
主站蜘蛛池模板: 久久青草精品免费资源站 | 在线观看免费视频网站色 | 国产高清一区二区三区视频 | 香蕉tv亚洲专区在线观看 | 香蕉成人在线视频 | 图图资源网亚洲综合网站 | 久久久毛片免费全部播放 | 日本在线免费 | 色一欲一性一乱一区二区三区 | 羞羞视频免费网站在线 | 日本精品在线视频 | 欧美一区永久视频免费观看 | 精品欧美成人高清视频在线观看 | 一级毛片aaa片免费观看 | 一级毛片aaaaaa免费看 | 久久久久久免费播放一级毛片 | 赘婿动画在线观看免费完整版 | 九色在线观看 | 国产免费一级片 | 国产精品久久久亚洲第一牛牛 | 亚洲综合欧美日韩 | 日韩欧美精品在线观看 | 日本最新免费二区三区 | 国产色在线com | 免费在线观看亚洲 | 国产清纯91天堂在线观看 | 欧美黑人粗硬大在线看 | 理论在线视频 | 四虎影院海外永久 | 毛片在线看免费版 | 久久六视频 | 99视频免费观看 | 久久免费观看国产99精品 | 色噜噜国产精品视频一区二区 | 国产成人精品亚洲2020 | 一级毛片在线免费视频 | 国产一级特黄在线视频 | 特级毛片永久久免费观看 | 日韩色视频一区二区三区亚洲 | 欧美视频xxxxx | 在线观看国产三级 |