综合久久影院-综合久久伊人-综合久久一区二区三区-综合久久五月天-亚洲欧美日韩国产一区图片-亚洲欧美日韩国产一区二区三区精品

Muen
News

News

Enterprise service provider

location : Home > News > Technical information

The reason and check method of inverter low voltage and overload trip

2023-05-20 12:17:11

Reasons for inverter low voltage trip


1. The low voltage of the inverter mainly refers to the low voltage of the intermediate DC circuit. Generally, the reason for the low voltage of the intermediate DC circuit comes from two aspects:


(1) Low voltage from the power input side


Under normal circumstances, the power supply voltage is 380V, and the allowable error is -15%~10%. After three-phase bridge full-wave rectification, the intermediate DC voltage value is 513V. In some cases, the power line voltage is small and the voltage fluctuation will not be The low voltage trip of the inverter will only cause the inverter to operate if the effective value of the grid voltage is between 80% and 85% of the rated value and the duration exceeds one cycle. The low voltage on the input side of the power supply is mainly due to the fluctuation of the grid voltage or the switching of the main power line, the power supply sine wave amplitude is affected by the lightning strike, the transformer of the power plant itself is overloaded or the load is unbalanced, etc.


(2) Low voltage from the load side


The reasons for this are mainly the start-up and application of large equipment, line overload, or starting large motors. The frequency converter is composed of rectifier and inverter. Through the research of the inverter, the low voltage of the inverter refers to the low voltage of the middle DC loop (that is, the input voltage of the inverter is too low). General frequency converters have protection functions of overvoltage, loss of voltage and instantaneous power failure. The inverter device of the inverter is divided into GTR and IGBT. When the inverter device of the inverter is GTR, once the voltage is lost or the power is cut off, the control circuit will stop outputting the signal to the drive circuit, so that the drive circuit and GTR all stop working, the motor It will be in free braking state. When the inverter device is IGBT, after the voltage loss or power failure, the inverter will be allowed to continue to work for a short time td. If the voltage loss or power failure time is totd, the inverter will protect itself and stop running. Generally, td is between 15 and 25 ms, and the power supply “shaking” time is generally more than a few seconds. The inverter will protect itself and stop running, so that the motor stops. Therefore, to solve the problem of inverter low voltage trip can not start from the inverter's inherent time td and voltage loss time to, but must start from the amplitude of the voltage drop.


2. Solutions for inverter low voltage trip:


There are two key points to be solved to solve the problem of inverter low voltage trip:


(1) It is necessary to select the inverter with IGBT inverter device;


(2) It is necessary to select the inverter that can still work normally under the condition of large voltage loss.


The motor can rotate, but the running current exceeds the rated value, which is called overload. The basic reflection of overload is that although the current exceeds the rated value, the magnitude of the excess is not large, and generally a large inrush current is not formed.


The reason and inspection method of inverter overload trip


1. The main reason for inverter overload


(1) Malfunction, the current detection part inside the inverter fails, and the detected current signal is too large, causing a trip.


(2) The mechanical load is too heavy. The main feature of the heavy load is that the motor heats up and can be found by reading the running current from the display.


(3) The three-phase voltage is unbalanced, which causes the operating current of a certain phase to be too large, resulting in overload tripping. It is characterized by unbalanced motor heating, which may not be found when the operating current is read from the display (because the display only shows one Phase current).


2. Check method of whether the inverter is overloaded


(1) Check whether the three-phase voltage on the motor side is balanced. If the three-phase voltage on the motor side is unbalanced, then check whether the three-phase voltage on the output side of the inverter is balanced. If it is not balanced, the problem is within the inverter.


If the voltage at the output of the inverter is balanced, the problem lies in the line from the inverter to the motor. Check whether the screws of all terminals are tightened. If there is a contactor or other electrical appliances between the inverter and the motor, It should be checked whether the terminals of the related electrical appliances have been tightened and the contact conditions of the contacts are good.


If the three-phase voltage on the motor side is balanced, you should understand the operating frequency at the time of tripping: if the operating frequency is low and vector control (or no vector control) is not used, first reduce the U/f ratio, if it can still drive the load , It means that the original preset U/f ratio is too high, the peak value of the excitation current is too large, and the current can be reduced by reducing the U/f ratio;


If the load can not be moved after the reduction, you should consider increasing the capacity of the inverter; if the inverter has vector control function, the vector control method should be used.


(2) Check whether the motor heats up. If the temperature rise of the motor is not high, first check whether the electronic thermal protection function of the inverter is preset properly. If the inverter still has a margin, the preheating of the electronic thermal protection function should be relaxed. Set value.


If the temperature rise of the motor is too high, and the overload is normal overload, it means that the motor is overloaded. At this time, whether the transmission ratio should be properly increased to reduce the load on the motor shaft. If it can be increased, increase the transmission ratio. If the transmission ratio cannot be increased, the capacity of the motor should be increased.


General purpose frequency converter


label

QR code

The public,

Mobile station
The public, Mobile station

Contact

未標(biāo)題-8.png 0755-81719517
未標(biāo)題-10.png0755-81719530 未標(biāo)題-11.png[email protected]
未標(biāo)題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

Navigation

Home          About

Product      Case

Solution      Service

Job      News

Contact          

Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號(hào):粵ICP備12045920號(hào)
主站蜘蛛池模板: 国产精品国产三级国产爱网 | 五月天堂网 | 国产成人亚洲综合欧美一部 | 99热这里只有精品国产在热久久 | 国产精品九九免费视频 | 黄色视屏在线 | 日日干日日操日日射 | 精品日韩欧美国产一区二区 | 自拍视频在线免费观看 | 亚洲逼| 日本精品在线视频 | 最新一本大道香蕉综合 | 亚洲欧美一区二区三区 | 成人精品视频一区二区三区尤物 | 久久九九精品一区二区 | 亚洲精品国产三级在线观看 | 曰本毛片 | 国产资源在线看 | 成人免费看视频 | 天堂网在线www资源在线 | 高清国语自产拍免费视频国产 | 超级乱淫视频播放日韩 | 成人久久久观看免费毛片 | 男女做羞羞的视频 | h肉动漫在线观看免费资源 h肉动漫在线观看高清 | 免费观看大片毛片 | 日韩欧美视频一区二区 | 五月天婷婷激情网 | 中文国产成人精品久久下载 | 亚洲精品中文字幕无乱码麻豆 | 乱一色一一区二区三区 | 亚洲国产精品成人午夜在线观看 | 人蛇大战4免费完整版 | 精品一区精品二区 | 亚洲精品国产手机 | 四虎新网站 | 国产精品国产精品 | 日韩欧美一区二区三区 | 欧美激情久久久久久久大片 | 国产精品毛片在线完整版sa | 天天艹天天艹 |